Gas Leak Repair
Refrigerant leaks degrade performance and risk environmental damage. Electronic leak detection, nitrogen pressure testing and certified brazing restore system integrity.
Vibration-fatigued brazed jointsCorroded or pitted evaporator coilsMechanical damage to pipeworkFailed schrader valveThermal stress cracks

COMPONENT_MACRO // FLT_003
Symptoms
- 01Gradual loss of cooling capacity
- 02Oil staining at fittings
- 03Hissing near pipework
- 04Low suction pressure
Probable causes
Vibration-fatigued brazed joints
Corroded or pitted evaporator coils
Mechanical damage to pipework
Failed schrader valve
Thermal stress cracks
Diagnostic checklist
01Electronic leak detector sweep of all joints
02Nitrogen pressure-test at 1.5x operating pressure
03Bubble-test suspect fittings
04Recover remaining refrigerant
05Brazing repair with nitrogen purge
06Pressure-test and vacuum to 500 microns
07Recharge to design weight